HVA68TD VLF high voltage test set

HVA68TD

HVA68TD VLF high voltage test set

HVA68TD

Art. number:
Date published 25.01.2024
Unavailable
Price and Delivery
Fill the request form below to receive a price and delivery offer

THE NEW MEMBER OF OUR SMARTVLF® SERIES

The HVA68TD is a truly compact and portable VLF test set that determines the condition of medium voltage cables with a voltage rating up to 46 kV (acc. to IEEE 400.2-2013).
It performs VLF and DC testing, as well as sheath testing with sheath fault location mode (additional fault probe needed). 

The high output power of the HVA expands greatly the load possibilities. It allows testing longer cables or several phases in parallel. The integrated Tan Delta diagnostics unit enables a straightforward condition assessment of the cable system.

The new HVA68TD is more than just a VLF tester. In addition to VLF testing & Tan Delta diagnostics capability, it allows to pre-locate arcs in the cable insulation. This makes the HVA68TD the smartest VLF test set available.

 ARC PRE-LOCATION (APL) 

A NEW DIMENSION FOR VLF TESTING

VLF withstand tests are used to detect weaknesses in the cable insulation. While a healthy cable is passing the voltage withstand test unharmed, a cable with pre-damaged insulation will break down during this test, resulting in an arc.

Arc Pre-Location information adds additional value to traditional VLF testing, which helps to save time and cost in the subsequent cable fault location process. 

Performance: Best in class output power combined with outstanding TD diagnostics features. 

Duty cycle: Operating time of these test sets is not thermally limited; they may operate continuously.

Connectivity: On-site, no external PC is needed. All results can be downloaded later via USB or Bluetooth for further investigation and easy reporting with the b2 ControlCenter.

 Safety first: Two independent discharge devices (electronic & mechanical) plus an integrated 12 kV backfeed protection system (at 50/60 Hz).

MWT: The HVA68TD offers Monitored Withstand Testing, a combination of withstand testing & Tan Delta diagnostics in compliance with the guide IEEE 400.2.

Flexible high voltage connection options: Our HV test leads enable a simple and safe connection between HVA & test object. They are available in different lengths and are quickly exchangeable.

Output voltage max. 68 kVpeak, 48 kVrms
Output load* 2 μF @ 0.1 Hz @ 44 kVrms

Dimensions
L x W x H*

466 x 340 x 510 mm / 
18.3 x 13.4 x 20.1 inch
Weight 63 kg / 139 lbs

YOUR BENEFITS

 pure sinusoidal output voltage (load-independent)
  • 12 kV transient protection (50 Hz)

  • Dual Discharge Device (DDDTM), integrated electronic and mechanical discharge devices

  • sheath fault pinpointing
    (in combination with sheath fault locator, not included)

  • easily exchangeable HV test lead
  • safe communication over Bluetooth
  • large color display (4.3")
  • programmable test sequences with a tailor-made software tool
  • download reports from the device via USB flash drive
  • vacuum bottle test

TECHNICAL DATA

Output characteristics

 

 

 

Output voltage

VLF sine wave

0 ... 48 kVrms / 0 ... 68 kVpeak

DC

-68 kV ... 68 kV

VLF square wave

0 ... 68 kV

Sheath test

0 ... 15 kV (negative polarity)

Voltage setting resolution

0.1 kV

AC frequency range

0.01 Hz..... 0.1 Hz

Frequency setting resolution

0.01 Hz

 

 

Output current

AC

56 mArms max.

DC

88 mA max.

Sheath test trip current

0.1 ... 5 mA

Sheath fault location

35 mA max.

Duty cycle

Continuous, no thermal limitation of operating time

 

High voltage tests

 

Test types

VLF withstand test | VLF Tan Delta test | Monitored Withstand test | DC test | Sheath test | Vacuum bottle test

Sheath fault location

pulse / period: 1:3 / 4s, 1:5 / 4s, 1:5 / 6s, 1:9 / 6s

(sheath fault locator not in scope of supply)

Test modes

Manual mode

Automatic test sequences (user definable)

Arc management modes

Burn on arc

Trip out on arc

 

Compliance

VLF withstand testing according to IEEE 400.2 & test standards DIN VDE 0276-620 (CENELEC HD 620 S2), DIN VDE 0276-621 (CENELEC HD 621 S1)

AC and sheath testing according to IEC 60502-2 / IEC 60229

 

Metering

 

Load 10 nF ... 10 µF

 

 

 

Tan Delta

TD range

0.1 ... 999 E-3

Resolution

single: 0.1 E-3 | mean: 0.01 E-3

Accuracy

± 0.1 E-3

Load 1 nF ... 10 nF

TD range

0.1 ... 999 E-3

Resolution

single: 0.1 E-3 | mean: 0.01 E-3

Accuracy

± 0.3 E-3

 

Arc Pre-Location

Measuring range

80 m ... 10 km

Velocity range (v/2)

10 ... 150 m/µs

Resolution

0.1 m

 

Further characteristics

AC supply

190 ... 240 V, 50/60 Hz, 3.500 VA

Product safety

Backfeed protection: 12 kV at 50/60 Hz

Dual Discharge Device (integrated electronic & mechanical discharge device)

 

DHV1472_HVA68TD_data... PDF, 667.6 KB Download
b2_HVA68TD_Folder_EN... PDF, 1529.9 KB Download